|
Electrical
System Checks
Changes in the performance of the electrical system of a magnetic
particle inspection unit can obviously have an effect on the sensitivity
of an inspection. Therefore, the electrical system must be checked
when the equipment is new, when a malfunction is suspected, or
every six months. Listed below are the verification tests required
by ASTM E-1444-01.
Maximum Unit Output
A magnetic
particle unit should be checked regularly (daily) to verify that
the maximum
current output of its electrical
system has not changed over time. This check is performed by placing
a large diameter (typically 1 inch or more) copper or aluminum bar
between the contacts and energizing the circuit with the current
control set to the maximum value. The maximum amperage as recorded
by the system's ammeter should be noted and compared to the value
obtained when the unit was last certified or calibrated. A significant
drop or gradual decay indicates a problem with the unit that should
be corrected.
Internal Short Test
The internal short circuit testing is required to determine
the if current is "leaking past" the test article. Internal
electrical leakage will cause the test equipment to indicate current
is flowing through the component when it is actually bypassing
the component. The process for checking equipment for this condition
is to energize the system with nothing between the contact heads
and the amperage set to the highest output. If the ammeter shows
any current flow, internal shorting should be suspected.
Ammeter Check
It is important that the ammeter provide consistent
and correct readings. If the meter is reading low, over magnetization
will occur and possibly result in excessive background fluorescence. If ammeter
readings are high, flux density could be too low to produce detectable
indications. To verify ammeter accuracy, a calibrated ammeter
is connected in series with the output circuit and values are
compared to the equipment's ammeter values. Readings are taken
at three output levels in the working range. The equipment meter
is not to deviate from the calibrated ammeter more than +/- 10
percent or 50 amperes, whichever is greater. If the meter is found
to be outside this range, the condition must be corrected. It should
be noted that when measuring half-wave rectified current, the
readings should be doubled.
Quick Break Test
A quick break circuit is primarily used in three-phase, full-wave
rectified systems to ensure longitudinal magnetic fields maintain
their strength to the end of a component. Quick break circuits
cause the current to abruptly collapse or drop to zero at the
end of the activation cycle. By doing this, low frequency eddy
currents are produced close to the surface of a component. These
eddy currents help extend the useable longitudinal field to the
ends of the component. To determine if a quick break system is
functioning properly, an oscilloscope is often used. By observing
the sine wave of the current, it can be determined if current drops
abruptly when the circuit is interrupted.
Shot Timer Check
When a timer is used to control the shot duration,
the timer must be calibrated. ASTM E-1444 -01 requires the timer
be calibrated to within +/- 0.1 second. A certified timer should
be used to verify the equipment timer is within the required tolerances.
|